Design and Construction Practices for Firestopping in Accordance with FM Standards for Structurally Critical Facilities
Latest News4 min read

Design and Construction Practices for Firestopping in Accordance with FM Standards for Structurally Critical Facilities

FM-compliant Firestop Design and Construction Practices Forming the First Line of Defense for Critical Facilities

In modern critical infrastructure such as data centers, telecom equipment rooms, high-voltage direct current converter stations (HVDC) and lithium battery energy storage systems (BESS), firestop systems are not only part of a building's passive fire protection but also the primary barrier to prevent the spread of fire, smoke and toxic gases. As the international risk-control standards setter, FM’s published Data Sheets 5-14, 5-25, 5-31, 5-32, 5-33 provide specific and rigorous design and construction requirements for sealing openings in fire-resistance rated assemblies.

  • Key FM requirements for firestopping
  1. FM-approved systems must be used Whether cables, cable trays, busbars, ducts or pipes, any penetration through fire-rated walls or floors must be sealed using FM Approved or Listed firestop systems (refer to DS 5-14, 5-31, 5-32, 5-33).
  • Fire-resistance rating must match the penetrated assembly

FM requires that the fire-resistance duration of the firestop system must not be less than the fire rating of the wall or floor being penetrated, for example:

  • Telecom/power equipment rooms and lithium battery energy storage areas: 2-hour fire rating (DS5-14, 5-33)

  • UPS rooms, data processing equipment rooms: 1-hour fire rating (DS5-32)

  • Valve halls of HVDC converter stations and adjacent areas: 1-hour firestopping (DS5-25)

  • Leakage rating (L-Rating) requirements

For sensitive equipment areas (such as data centers and telecom rooms), FM also requires that the firestop system provide low air leakage performance in the pre-fire stage, with a leakage rate of ≤7 ft³/min/ft² (2.1 m³/min/m²) to control initial smoke ingress (DS5-145-32).

  • FM4991: certification assurance for professional installation

High-standard products must be correctly installed by professional installation teams to achieve complete fire performance. FM DS5-31 explicitly recommends selecting companies that hold FM4991 firestop contractor certification to perform firestopping work.

Why choose an FM4991-certified contractor?

  • Robust quality control system: including material management, construction procedures, inspection processes and complete records
  • Certified construction personnel: regular training, testing and requalification to ensure skill levels
  • Strong traceability of works: every penetration has construction records and tag numbers
  • Higher compliance and recognition: greater credibility during insurance, review and owner acceptance

For example, Shanghai Tengxi Construction Engineering Co., Ltd., as an FM4991-certified professional contractor, possesses systematic quality management capabilities and can provide full-process, traceable, international-standard firestopping solutions for high-grade facilities.

  • Best practice summary

The following combination ensures firestopping meets FM requirements and achieves optimal protection:

  • FM Approved firestop materials (matching fire-resistance and leakage ratings)
  • FM4991-certified contractor professional installation (ensuring construction methods and quality control)
  • Standardized labeling and acceptance procedures (facilitating management, review and maintenance)

This product + installation + management trinity is the most reliable FM-compliant firestopping practice for current data centers, telecom, power, energy and other facilities.