In high-risk, high-cleanliness semiconductor manufacturing environments, firestop systems are no longer merely structural components that prevent flame spread; they are key facilities that maintain cleanroom contamination control, pressure differential stability, and rapid post-disaster recovery capability. Once a fire occurs, smoke backflow, chemical leaks, or HVAC failure can cause major damage to product yield and production continuity. Therefore, the design and acceptance of firestop must move beyond traditional experiential practices toward standardized, systematic, and traceable full-process management.
According to FM DS 7-7 "Semiconductor Manufacturing Facilities" specification, all penetrations through firewalls, floors, and ceilings must use FM-certified firestop materials and be installed by contractors holding FM4991 certification. The fire-resistance rating of the firestop system should be equal to or greater than the original structure, and penetrations in equipment areas must have good airtight performance, with a maximum air leakage of 2.1 m/min per square meter not to be exceeded, to prevent rapid spread of smoke and particles into critical process areas during the early stages of a fire. FM standards further require at least one annual inspection of firestop conditions to ensure long-term system effectiveness.
FM DS 1-56 "Cleanrooms" also stipulates that all pipes, cables, and utilities penetrating non-combustible floors and firewalls should be tightly sealed using approved materials, and a regular inspection mechanism should be established every six months, covering key areas such as walls, floors, and fire doors, to ensure zonal isolation integrity and blocking function. At the same time, building materials used in cleanrooms must meet the fire test requirements of ASTME84SDI0.4 (m/s^1/2)(g/g)(kW/m)^(2/3), and their smoke density index () must not exceed , in order to reduce the risk of smoke contaminating clean spaces during a fire.
On this basis, firestop materials must also pass cleanroom outgassing tests and contamination analysis to ensure they do not release volatile molecular contaminants (AMC, Airborne Molecular Contaminants) at ambient or elevated temperatures, thereby avoiding contamination of process equipment or products. According to international standards such as ISO 14644-8 SEMI F21, materials should pass ASTME595 GC/MSTMLCVCM testing and gas chromatography–mass spectrometry analysis to confirm that their total mass loss () and condensable volatiles () are within acceptable ranges, and they must not contain high-risk components such as siloxanes, chlorinated gases, or organic solvents before being applied in high-class clean spaces, achieving the dual goals of "fire protection" and "contamination prevention."
ULAt the same time, firestop systems should also have excellent airtightness and watertightness. According to certification standards, the grade is used to assess the air leakage performance of a 75 Pa firestop system under standard pressure differential (), which is an important basis for maintaining cleanroom pressure balance and controlling microcontamination; while the grade represents the material's ability to resist leakage under 72 hours of hydrostatic pressure, suitable for areas where condensate, cleaning fluids, or humid environments are present. Therefore, ULL/W ratings have become an important technical reference for selecting firestop systems in cleanroom projects.
As an FM4991 certified firestop contractor, Shanghai Tengxi Construction Engineering Co., Ltd. has proposed a set of systematic cleanroom firestop solutions that fully integrate standards systems such as from preliminary drawing review, material selection, to on-site construction inspection and issuance of testing reports FMULGBIAS, and combine third-party inspection mechanisms to provide internationally effective inspection services and compliance declarations.
Through this integrated process, enterprises can effectively implement cleanroom fire strategies from "contamination control" to "operational resilience," achieving the goals of no interruption, no contamination, and no loss.
TKC — Science-based Industrial Safety & Protection
For more technical details or a professional assessment, please contact the TKC expert team.